The transmitter and valve as a 1oo2 trip architecture query

2010-10-25

A transmitter and its signal will be used as a second shutdown input with 1oo2 voting and the control valve will be used as a second shutdown mechanism. (Pls see the attachement Figure 15-3.) common equipment is used, the BPCS cannot be considered an independent layer of protection. It is said that this case only valid that the control valve will have sufficient tight shutoff performance to protect against the against the hazard by itself. If this is not the case, then this design cannot be used.
My query what kind of control valve(ex. Fail close,...) can be suitted for this situation and what kind of process (ex. Pump Min flow path ...)will apply this design.
BPCS control valve and its loop can not be considered as layer of protection. And also this arrangement with two transmitters is not good as well, but it depends of hazid and hazop studies. In europe there is leakage rate classification you can find control valves(KKI can supply you valve with leakage class VI)which can be leak tight as well, but I would suggest to use 2oo3 voiting system and totally separate BPCS transmitter.I would even suggest to segregate shut down system(SIS) and BPCS and not feed any BPCS transmitter output to SIS system. This is much safer.


MORE NEWS

  • Twin MAF readings to the ECU
  • Double arrangement/48-inch butterfly valves
  • Triple eccentric butterfly valves
  • Butterfly valves to match flange types
  • Shanghai MeiYan Yi Pump & Valve Co., Ltd.
    MeiYan Yi butterfly valve Contact MeiYan Yi
    Shanghai Enine Pump & Valve Co., Ltd.
    Enine butterfly valve Contact Enine
    Shanghai Saitai Pump & Valve CO., Lid.
    Saitai butterfly valve Contact Saitai
    Shanghai Fengqi Industrial Development Co., Ltd.
    FengQi butterfly valve Contact FengQi